Residual Current circuit breaker (RCCB)(without overcurrent protection)ensure electrical safety in homes and similar situations, such as offices and other buildings as well as for industrial applications by protecting electrical installations against leakage Current reach to 30mA. Once a fault is detected, the Residual Current circuit breaker automatically switches off the electrical circuit to prevent risk to the people. Warranting reliability and safety for people and assets.
Main
Range | QJ65 |
Product name | QJ65 RCCB |
Product or component type | Residual current circuit breaker (RCCB) |
Device short name | RCCB |
Poles description | 4P |
Neutral position | Left |
[In] rated current | 80 A |
Network type | AC |
Earth-leakage sensitivity | 300 mA |
Earth-leakage protection time delay | Instantaneous |
Earth-leakage protection class | Type A |
Complementary | |
Device location in system | Outgoer |
Network frequency | 50/60 Hz |
[Ue] rated operational voltage | 220…240 V AC 50/60 Hz |
Residual current tripping technology | Voltage independent |
Rated breaking and making capacity | Idm 1500 A Im 1500 A |
Rated conditional short-circuit current | 10 kA |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 6 kV |
Contact position indicator | Yes |
Control type | Toggle |
Mounting mode | Clip-on |
Mounting support | DIN rail |
9 mm pitches | 8 |
Height | 91 mm |
Width | 72 mm |
Depth | 73.5 mm |
Net weight | 0.37 kg |
Colour | White |
Mechanical durability | 20000 cycles |
Electrical durability | AC-1: 15000 cycles |
Locking options description | Padlocking device |
Connections – terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule |
Wire stripping length | 14 mm for top or bottom connection |
Tightening torque | 3.5 N.m top or bottom |
Environment | |
Standards | EN/IEC 61008-1 |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution degree | 3 |
Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
Ambient air temperature for operation | -25…60 °C |
Ambient air temperature for storage | -40…85 °C |
If you have any needs , please fill out the form below and we will contact you as soon as possible.