Three-phase overvoltage and undervoltage protector

Three-phase

Overvoltage and undervoltage protectors are commonly used power protection devices used to protect power equipment from damage due to excessive or low voltage. Adjusting the parameters of the overvoltage and undervoltage protector can make it better adapt to the actual working environment and needs, and improve the safety and reliability of power equipment.

Additional information

Share To:

Product Parameter (Specification)

CodeTechnical ParameterMinimum Protection ValueMaxmum Protection ValueDefault Protection ValueFunction Description
P1Power-on delay time1s500s10sAfter external power cut,the time needed for power-on when power recovery.
U1Over-voltage protection value230V300V270VWhen the voltage is higher than the set value, the protector will cut off the line.
U2Over-voltage        recovery value225V295V265VWhen the voltage is lower than the set value, the protector will automatically reset.
U3Over-voltage     recovery delay time1s500s30sAfter voltage recovery,the time needed for automatic reset.
U4Over-voltage       protection action time0.1s30s1.0sWhen the voltage is higher than the set value,the time needed for protection action.
U5Under-voltage protection value140V210V170VWhen the voltage is lower the set value, the protector will cut off the line.
U6Under-voltage recovery value145V215V175VWhen the voltage is higher than the set value, the protector will automatically  reset.
U7Under-voltage recovery delay time1s500s30sAfter voltage recovery,the time needed for automatic reset.
U8Under-voltage   protection action time0.1s30s1.0sWhen the voltage is lower than the set value,the time needed for protection action.
U9Three phase voltage error value-9.50%9.50%0Correct the three phase voltage error.
U10Three phase voltage unbalance protection value20V99V20VWhen three phase voltage unbalance value is higher than the set value, the protector will cut off the line.
U11Three phase voltage unbalance recovery value5V94V20VWhen three phase voltage unbalance value is lower than the set value, the protector will automatically  reset.
C1Over-current protection value1A63A30AWhen the current is higher than the set value, the protector will cut off the line.
C2Over-current recovery delay time1s500s30sAfter current recovery,the time needed for automatic reset.
C3Over-current protection action time0.1s30s1.0sWhen the current is higher than the set value,the time needed for protection action.
C4Three phase current error value-9.50%9.50%0Correct the three phase current error.
C5Times of continuous over current protection020OFFWhen The times of continuous over-current protection exceeds the set value,the protector will cut off the line,then it needs to be opened manually.
message

Online Message

If you have any needs , please fill out the form below and we will contact you as soon as possible.

Related Products

View similar products to find what you want.

Three-phase electronic rail active energy meter

Single-phase Timing Switch

24Hour Auto off Types Analog Mechanical Control Switch

WGSPC-40

Get In Touch With Us

We’re here to help! Whether you have questions, need assistance, or want to learn more about our products and services.